The proposed QTS data center on Gordon Highway would have 236 diesel backup generators. The draft Georgia air permit would cap their combined nitrogen oxide emissions at 249 tons over any 12 consecutive months.
That is one ton below the applicable 250-ton threshold for major-source review under the federal Prevention of Significant Deterioration construction-permitting program, the state’s technical review explains. The cap is not a projection that the equipment will emit 249 tons every year. And the draft still requires QTS to apply for a separate Title V operating permit within 12 months of generator startup.
The equipment list for QTS ATL3, at 2883 Gordon Highway, includes 224 emergency generators for critical operations and 12 for building systems. The number of generators tells you how much backup equipment is proposed. It does not tell you how often all of it would run, or how much pollution any given month would produce.
What would the state see?
The proposed permit uses generator operating records and emissions calculations to track compliance. Fuel, load and hours help determine how much nitrogen oxide the machines are calculated to have emitted. That is different from continuously measuring nitrogen oxides at each exhaust outlet.
The draft would require QTS to notify Georgia’s Environmental Protection Division within 15 days after any calendar month above 20.75 tons of calculated nitrogen oxide emissions from the generators. It also calls for notice within 15 days after any 12-month total exceeds 249 tons. Look for conditions 7.4 and 7.6 in the draft. The monthly reporting threshold is an early warning; the rolling 12-month figure is the proposed emissions cap.
A useful question for the hearing: How will the public be able to see the monthly totals, and how would EPD check the calculations if multiple generators run at once during an outage?
How to comment
EPD’s official hearing notice says written comments are due by 4:30 p.m. Eastern on Thursday, December 3. Email air-permits.comments@dnr.ga.gov with the subject QTS ATL3 Air Quality Permit.
The public hearing is that evening, 6–7:30 p.m., in Room 260 on the second floor at 535 Telfair Street in Augusta. The notice limits oral statements to three minutes per speaker. This is a draft, not an issued permit.